limit value relay | MR 50 Ex

limit value relay | MR 50 Ex


581,00 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: MR50Ex
input:
1: standard signals 0/4 to 20 mA, 0/2 to 10 V DC, transmitter supply approx. 16 V DC, max. 20 mA, inputs intrinsically safe:
alarm output A1, A2:
2R: 2 relays SPDT:
alarm output A3, A4:
00: not installed:
analog output:
00: not set:
AO: 0/4 to 20 mA; 0/2 to 10 V DC (+ 123,80 EUR) :
auxiliary voltage:
0: 230 V AC | ±10 % 50-60 Hz:
1: 115 V AC | ±10 % 50-60 Hz (+ 2,90 EUR) :
5: 24 V DC | ±15 % (+ 35,20 EUR) :

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

The limit value relay MR50 has been designed for monitoring measuring values. Measuring value and programmed unit are shown in the display. The integrated transmitter supply offers direct connection of loop powered sensors. Simple
programming, up to 2 alarm outputs (SPDT) and optional available fully isolated free programmable analog output 0/4 mA to 20 mA; 0/2 V DC to 10 V DC meets the demand for different applications.

  • input standard signals 0/4 mA to 20 mA, 0/2 V DC to 10 V DC
  • measuring range programmable
  • max. 2 alarm outputs
  • isolated analog output 0/4 mA to 20 mA, 0/2 V DC to 10 V DC


specifications:

auxiliary energy
auxiliary voltage:       
230 V AC ±10 %, 115 V AC ±10 %, 24 V DC ±15 %
Um = 253 V AC or 125 V DC
(terminals 11 and 13)
power consumption: max. 5 VA
operating
temperature
:
-10°C to +55°C
CE conformity:ATEX-directive 2014/34/EU
standards:EN 60079-0:2006 EN 60079-11:2007
EN 61241-0:2006 EN 61241-11:2006
EMC-directive / standard:2014/30/EU / EN 61326-1:2013


inputs
explosion protection:Ex II (1) G [Ex ia] IIC/IIB or II (1) D [Ex iaD]
approval:TÜV 08 ATEX 554329
fault detection:break of wire in the measuring circuit


input  
input:                                                  
0/4 mA to 20 mA; 0/2 V DC to 10 V DC
Ri: current 10 Ω,
voltage 10 kΩ

fault detection:break of wire in the measuring circuit
(terminals 45, 46 and 47)
accuracy:<0.1 %, ±1 digit
temperature coefficient: 0.01 %/K

 
safety data
max. no load voltage U0: 18.9 V
max. short circuit curr. I0:       
92.5 mA
max. output power P0:       
580 mW
resistance R:       
272 Ω
characteristics:      trapezoidal
internal inductivity:     
4 μH
internal capacity:     
1.2 nF
transmitter supply:     
approx. 16 V DC max. 20 mA
(terminal 48)
      

explosion protection       

Ex ia/IIC:       
max. ext. inductivity: 2.3 mH
max. ext. capacity: 0.12 μF

Ex ia/IIC:       
max. ext. inductivity: 0.1 mH
max. ext. capacity: 0.22 μF
Ex ia/IIB:       
max. ext. inductivity: 5 mH
max. ext. capacity: 0.76 μF
       
At connecting of externally supplied active intrinsically safe circuits the rules for the interconnection of intrinsically safe circuits have to be observed.
max. values:       Ui: 30 V
Ii: 52 mA
Pi: 980 mW
       

outputs
relay SPDT:   < 250 V AC < 250 VA < 2 A
cosφ ≥ 0.3,
< 300 V DC < 40 W <2 A
(terminals 21, 22, 23; 25, 26, 27).

analog output: 0/4 to 20 mA, burden ≤500 Ω;
0/2 to 10 V burden >500 Ω, isolated,
output changes automatically
(burden dependent).

accuracy: 0.2 %;TK 0.01 %/K
for connection at electrical equipments with supply voltage of max. 230V (terminals 17 and 18)

fault function:    break of wire in the measuring circuit:
analog output 0 mA, < 3.6 mA or >21.5 mA
→ alarm contact(s) min. or max. programmable
       

display:   
graphic LCD display, 128 x 64 pixel,
with white back-light

       

housing     

type:  
polyamide (PA) 6.6 , UL94V-0 acc. to DIN EN 60715
weight:  
approx. 450 g
connection:  
screw terminals 0.14 mm2 to 2.5 mm2
(AWG 26..14)

ingress protection:  
housing IP30, terminals IP20, BGV A3




For further details p.r.t. data sheet:





instruction manual as .pdf:


 

 

 