general information:
Isolating signal converters TW500 are a cost-efficient option for galvanic isolation of 0/4...20 mA current signals. Up to 3 channels are deliverable in one 22.5 mm DIN rail housing.
specifications:
input | |
current: | 0(4) to 20 mA DC |
max. current: | 100 mA |
max. voltage: | 27 V DC |
voltage drop: | <2.7 V (I ≤ 20 mA) |
test voltage: | 4 kV DC input / output |
rated voltage: | 630 V AC/DC acc. to VDE 0110 group 2 |
operating temperature: | -20°C to +60°C |
CE conformity: | EN 61326-1:2013; EN 60664-1:2007 |
output | |
current: | 0(4) to 20 mA |
max. current: | max. input current |
burden: | <1,200 Ω (I ≤ 20 mA) |
rise time (t90): | <30 ms |
accuracy: | <0.1 % |
burden error: | <0.0008 %/Ω |
temperature coefficient: | <0.001 %/°C |
ripple: | <0.2 % |
housing | |
construction type: | standard case polycarbonate 8020 UL94V-1 acc. to DIN EN 60715:2001-09 |
weight: | approx. 140 g |
connection: | screw terminals, max. 2.5 mm2 |
ingress protection: | case IP30, terminals IP20 acc. to BGV A3 |
For further details p.r.t. data sheet:
instruction manual as .pdf: