Deutsch  English 


universal isolating amplifier | TV125L

universal isolating amplifier | TV125L


117,50 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: TV125L
model:
125L: auxiliary voltage 18 to 30 V DC:
125LP: auxiliary voltage 18 to 30 V DC (with mounting rail bus connection) (+ 7,35 EUR) :
input:
10: 0/4 to 20 mA and 0/2 and 10 V DC:
auxiliary voltage:
5: 18 to 30 V DC:
options MA:
01: push-in terminals (pluggable) (+ 7,35 EUR) :
accessories:
PRVK: power rail supply terminal (+ 4,55 EUR) :

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

Isolating amplifiers of the series TV125L are suitable for potential isolation or for conversion of unit signals. The universal layout of the inputs and the output enables a broad range of applications with only one type of device. The plug-in terminal strips enable simple and time-saving wiring. The configuration is also quick and easy with the front DIP switches.

  • safe galvanic isolation between input / output / auxiliary voltage with reinforced isolation in accordance with DIN EN 61010-1
  • step response T90 40 ms
  • output deviation <0.2% of the limit value
  • overload protection of the current input with automatically resetting fuse
  • operating display and status messages via two-colour LED
  • configuration via front DIP switches
  • plug-in terminal strips
  • narrow installation width of 12.5 mm for carrier rail mounting TS 35


specifications:

auxiliary power

auxiliary voltage: 18 to 30 V DC
power consumption:
<0.5 VA
conformity: CE, directive 2004/108/EG
EMV:DIN EN 61326-1: 2013-07
standards:DIN EN 61010-1: 2011-07,
DIN EN 61010-2-30: 2011-07
rated voltage:300 V AC/DC acc. to DIN EN 61010-1
with overvoltage category 2 and degree of contamination 2 between all circuits. Safe separation with amplified isolation.
test voltage:3 kV AC, 50 Hz, 1 min  input / output / auxiliary power


environmental conditions
working temperature:-10°C to +60°C
storage temperature:-20°C to +60°C
air humidity:<95 % (no condensation)


inputs
voltage input:switchable 0 V to 10 V or 2 V to 10 V.
Ri = 47 kΩ. Max. overload 32 V AC/DC
current input:switchable 0 mA to 20 mA or 4 mA to 20 mA.
Ri = 48 Ω + 15 Ω (RiPTC).
Max. overload 32 V AC/DC acc. to DIN EN 61010-2-30


output
current output:switchable 0 mA to 20 mA or 4 mA to 20 mA.
Load <150 Ω.
step response:40 ms
standard error:<0.2 % of final value
temperature coefficient:<0.01 % / K


housing
material:Polyamide (PA) 6.6, UL94V-0
weight:91 g
ingress protection:housing IP30, terminals IP20 BGV A3
colour:light grey
installation width:12.5 mm
dimensions (HxT):108 x 114 mm
installation:carrier rail mounting TS35 DIN EN 60715







For further details p.r.t. data sheet:




instruction manual as .pdf:

 

 

 

Warenkorb

Sie haben noch keine Artikel in Ihrem Warenkorb.

Warenkorb »

Herzlich willkommen

E-Mail-Adresse:
Passwort:
Passwort vergessen?

Top Artikel