Deutsch  English 


temperature measuring transducer | TC125

temperature measuring transducer | TC125


203,00 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: TC125
model:
125L: housing width 12.5 mm, auxiliary voltage 24 V DC +/- 15 %:
125LP: housing width 12.5 mm, auxiliary voltage 24 V DC +/- 15 % with carrier rail bus connection (+ 7,00 EUR) :
125M: housing width 12.5 mm, wide-range power supply 20 to 125 V DC, 20 to 253 V AC (+ 21,00 EUR) :
input:
00: installation of device type TC125 in zone 2, acc. to ATEX ignition protection typ "ec" possible:
Ex: In case of installing the devices out of the ex-zone: Input and transmitter feed are intrinsically safe in accordance to ignition protection type “ia” for zones 0 and 20. The devices types TC125L and TC125LP may be installed in zone 2 according to ATE (+ 48,20 EUR) :
options MA:
01: push-in terminals (pluggable) (+ 7,35 EUR) :
02: upscaling error case: outputs >21 mA, >10.5 V (standard downscaling: outputs 0 mA, 0 V):
accessories:
PRVK: power rail supply terminal (+ 4,55 EUR) :

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

The TC125 temperature transducers convert signals of temperature resistance (Pt100 / Pt1000) or thermocouples (J, K, S) into standard
signals (0/4..20 mA and 0/2..10 V).

Applications with signals from the Ex area or requirements of higher enviromental immunity require galvanic isolation. This applies espacially to grounded temperature sensors.

The TC125 therfore has a 3-way electrical isolation between input, output and auxiliary voltage. There are 8 preconfigured measuring ranges available for PT100, PT1000 and thermocouples which can be adjusted easily with trim potentiometers with regard to zero point and range. When using thermocouples, an internal temperature compensation - by measuring the terminal temperature - can be activate or deactivate.

With an intrinsically safe input (EX) the use in Ex-applications is possible.

  • universal input for Pt100, Pt1000, thermocouple J / K / S
  • thermocouples with temperature compensation that can be switched off
  • available with intrinsically safe inputs, type of protection ia, zone 0/20
  • pre-scalings that can be adjusted using trim potentiometers
  • analog output 0(4) .. 20 mA and 0/(2)..10 V, simultaneously
  • wide range AC / DC or 24 V DC supply
  • optional auxiliary voltage supply via DIN rail bus


specifications:

explosion protection
Ignition protection type ia (intrinsically safe inputs):                                           
type: TC125L-Ex / TC125LP-Ex / TC125M-Ex
zone 0/1/2: II (1) G [Ex ia Ga] IIC
zone 20/21/22: II (1) D [Ex ia Da] IIIC
ignition protection type ic (intrinsically safe inputs +
zone 2 installation):
type: TC125L-Ex / TC125LP-Ex
zone 2: II 3 G Ex ec [ic] IIB T4 Gc
limit values -
intrinsically safe curcuit:
Uo = 2.2 V; Io = 4.2 mA;
Po = 2.4 mW Ci = 33 nF;
Li ≈ 0 mH Co = 10.9 uF at Lo= 50 mH
ignition protection typ ec (without intrinsically safe inputs, zone 2 installation): type: TC125L / TC125LP
zone 2: II 3 G Ex ec IIB T4 Gc


auxiliary energy / voltage

TC125M (wide-range power supply):85...250 V AC (47..63Hz), <1.5 W, <3 VA
20...125 V DC, <1.5 W

TC125L/LP (DC and power rail):24 V DC +/-15 %, <1.5 W


CE conformity

low-voltage directive:2014/35/EU: EN 61010-1, EN 60664-1
EMV:2014/30/EU: EN 61326-1
ATEX:2014/34/EU: EN 60079-0, EN 60079-11,
EN 60079-7


rated voltage:EN 60664-1: 250 V AC, overvoltage category 2,
degree of contamination II
EN 60079-11: 250 V AC / 125 V DC
test voltage:3 kV AC between auxiliary voltage / input / output
operating temperature:-10°C to +60°C
storage temperature:-20°C to +80°C
air humidity:10 % to 90 % (no condensation)


measuring inputs
accuracy

standard error:0.2 %
liniarity error:0.05 %
temperature error:0.01 %/K
output current / voltage:0.1 %


resistance sensor
switching type:3-wire-compensation
(2-wire connection with elect. bridge)
line resistance:max. 100 Ohm (integration of safety barriers possible)
break of sensor detection:yes
short circuit detection:yes


Pt100
measuring current:approx.1 mA
detection range:- 70°C to +850°C
zero point adjustment:approx. +/-8 Ohm (approx. +/-20°C)
end-value adjustment:approx. +/- 15 % of factory end value


Pt1000
measuring current:approx. 100 μA
detection range:-70°C to +260°C
zero point adjustment:approx. +/- 80 Ohm (approx. +/- 20°C)
end-value adjustment:approx. +/- 15 % of factory end value


thermo couple

cold junction compensation:yes, selectable
break of sensor detecion:yes
detaction range:J, Fe-CuNi: -70°C to +900°C
K, NiCr-Ni: -100°C to +1,250°C
S, PtRh-Pt90/10: 0°C to 1,800°C
zeropoint adjustment:approx. +/- 10 % of factory end value
end-value adjustment:approx. +/- 15 % of factory end value


analog outputs:0/2..10V: switchable, load < 5 mA, short cuircuit proof
0/4..20mA: 0/4..20 mA DC,
switchable, burden <600 Ohm, simultanouse use with voltage output possible
behavior in case of error:standard: 0 mA; 0 V (downscaling)
option 02: >21 mA; >10.5 V (upscaling)
transmission path:step response T90: <800 msec


housing
dimensions (B x T x H):12.5 x 114 x 108 mm
material:polyamid (PA) 6.6, light grey, flammability class V0 (UL94)
weight:120 g
ingress protection:IP20
screw terminals:0.2 mm2 to 2.5 mm2, AWG 24..14, removable encoded
push-in-terminals:0.5 mm2 to 1.5 mm2, AWG 25..16, (spring clamps) double connection (12 A between the connectors), removable encoded
power rail:8 A over entire bus system (supply via removable terminals 0.2 mm2 to 2.5 mm2, AWG 24..14




For further details p.r.t. data sheet:






instruction manual as .pdf:


 

 

 

Warenkorb

Sie haben noch keine Artikel in Ihrem Warenkorb.

Warenkorb »

Herzlich willkommen