Deutsch  English 


switch amplifier | TS125 / TS225

switch amplifier | TS125 / TS225


110,00 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: TSX25
model:
125L: housing width 12.5 mm, relay NO contacts, auxiliary voltage 24 V DC +/- 15 %:
125LP: housing width 12.5 mm, relay NO contacts, auxiliary voltage 24 V DC +/- 15 % (with mounting rail bus connection) (+ 7,50 EUR) :
125M: housing width 12.5 mm, relay NO contact, wide-range voltage supply 20 to 125 V DC, 20 to 253 V AC (+ 14,80 EUR) :
225M: housing width 22.5 mm, relay changeover contacts, wide-range power supply 20 to 125 V DC, 20 to 253 V AC (+ 22,00 EUR) :
explosion protection:
00: installation of the device TS125/TS225 in zone 2 permitted, in accordance with ATEX ignition protection type „n“:
Ex: in case of installing the devices outside the ex area: inputs intrinsically safe in accordance with ATEX ignition protection type "ia" for zones 0 and 20, the device TS125/TS225 may be installed in Zone 2 in accordance with ATEX ignition protection ty (+ 7,35 EUR) :
number of channels:
1: single channel:
2: dual channel (+ 21,90 EUR) :
F: single channel with additional error relay or parallel relay (+ 21,90 EUR) :
options MA:
01: push-in terminals (pluggable) for TS125 (+ 7,35 EUR) :
accessories:
PRVK: power rail supply terminal (+ 4,55 EUR) :

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

Switch amplifiers of the series TS125 and TW255 are used in switch cabinets for the conversion and isolation of digital switching signals, also in explosion-prone areas. The devices are available in one- or two-channel versions. Passive sensors, such as switching contacts, Namur initiators, or passive electronic outputs of external devices, can be connected to the intrinsically safe inputs.
The TS125 series in a 12.5 mm wide carrier rail housing offers relay outputs with NO function. The TW225 series in a 22.5 mm wide carrier rail housing offers relay outputs with changeover function. The plug-in terminal strips enable simple and time-saving
wiring. The configuration is also quick and easy with the front DIP switches.

  • 1 or 2 channel version
  • safe galvanic isolation between input / output / auxiliary voltage
  • functional safety up to SIL2 EN61508
  • inputs for switching contacts, Namur initiators or optocouplers
  • intrinsically safe inputs for connection of sensors in Ex zones 0 and 20
  • device installation in Ex zone 2 possible
  • galvanic isolation in accordance with the requirements for amplified isolation (EN60664)
  • switchable monitoring of the input circuit for wire breaks and short-circuit
  • relay outputs as normally open or changeover contacts (invertible effect)
  • wide-range power supply or 24 V DC
  • configuration via front DIP switches
  • pluggable coded terminal strips
  • housing width of 12.5 or 22.5 mm
  • Carrier rail mounting TS35 EN60715
  • operating display, indication of switching status and errors via LEDs


specifications:

explosion protection
gas: II (1) G [Ex ia Ga] IIC/IIB
dust:
II (1) D [Ex ia Da] IIIC
Intrinsically safe + zone 2: II 3 G nA nC [ic] IIB T4 Gc *)
protection class „n“:II 3 G nA nC IIB T4 Gc X *)


wide-range power supply
auxiliary voltage:20 V DC to 125 V DC and
20 V AC to 250 V AC, (47 Hz to 63 Hz), max.1.5 W
ATEX threshold:Uo = 8.7 V; Io = 19 mA; Po = 42 mW
Li = 20 μH;
Ci = 10 nF
IIB/IIIC:
Lo   100 μH   1 mH    100 mH
             Co   12.9 μF   7.3 μF   2.8 μF
IIC:      
Lo    100 μH   1 mH   100 mH
             Co    2.2 μF    1.2 μF   0.4 μF


24 V mains adapter

auxiliary voltage:
24 V DC +/-15 %, max. 1.5 W
ATEX threshold:Uo = 8.7 V; Io = 17 mA; Po = 37 mW
Li = 20 μH; Ci = 10 nF
IIB/IIIB:
Lo   100 μH   1 mH   100 mH
             Co   13.9 μF   7.3 μF  2.9 μF
IIC/IIIC:
Lo   100 μH   1 mH   100 mH
             Co    2.2 μF    1.3 μF  0.4 μF


combined data
Um (acc. to ATEX): 
253 V AC / 125 V DC
test voltage:3 kV AC between input/output/auxiliary voltage
working temperature:-10°C to +60°C
storage temperature:-20°C to +80°C
air humidity:10 % to 90 % (non-condensing)


measuring inputs (acc. to EN60947-5-6 Namur)                                               

open circuit voltage:approx. 8 V
Short circuit current:approx. 8 mA
switching points:
inactive <= 1.2 mA,
active >= 2.1 mA, hyst. < > 0.5 mA
error recognition:             
wire break: <0.2 mA
short circuit: >7 mA


relay outputs

switching voltage:
<250 V AC <2 A <500 VA
<125 V DC <0.2 A <25 W
< 30 V DC <2 A <60 W
switching frequency:max. 5 Hz
delay:max. 30 ms


housing
dimensions (W x D x H):TS125: 12.5 x 114 x 108 mm
TS225: 22.5 x 114 x 108 mm
material:PA6.6, light grey, flammability class V0 (UL94)
weight:TS125: 120 g; TS225: 140 g
ingress protection:IP20
terminals:0.2 mm2 to 2.5 mm2, AWG 24..14
removable coded terminals


functional safetySIL2 in accordance with EN61508
(specific data upon request)



*) Manufacturer's certificate, requires installation in an earthed, conductive housing (minimum ingress protection IP54)




For further details p.r.t. data sheet: