Deutsch  English 


current and voltage transducer | CVT 500

current and voltage transducer | CVT 500


188,00 EUR

 inkl. 19 % USt  -> Preis zzgl. Versandkosten

Lieferzeit bzw. Fertigungszeit variiert - bitte erfragen!

Art.Nr.: CVT500
current measuring ranges:
0: not installed (at custom range voltage):
1/5: standard range 0 to 1 A and 0 to 5 A AC/DC:
custom measuring range (+ 45,00 EUR) :
custom measuring range 0...xx A (please quote):
voltage measuring ranges:
0: not installed (at custom range current):
125/250: standard range 0 to 125 V and 0 to 250 V AC/DC:
custom measuring range (+ 45,00 EUR) :
custom measuring range 0...xx V (please quote):
auxiliary voltage:
0: 230 V AC | ±10 %:
5: 24 V DC | ±15 %:

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Produktbeschreibung


general information:

Transmitter CVT 500 convert current or voltage signals to proportional industry standard signals. Direct measurement of currents up to 5 A and voltages up to 400 V are possible. For larger alternating currents a current converter and for larger alternating voltages a voltage converter is needed.

  • measuring input for DC- and sinusoidal AC-signals
  • arithmetic average value measurement RMS calibrated
  • frequency range 40 Hz to 200 Hz


specifications:

auxiliary energy
auxiliary voltage:       
230 V AC ±10 % or 24 V DC ±15 %
frequency AC: 47 Hz to 63 Hz
power consumption:<3 VA
operating temperature:-10°C to +50°C
CE conformity:EN 61326-1:2013; EN 60664-1:2007

 
inputs  
accuracy: ≤ 0.5 % (≤ 0.2 % single adjustment)
frequency AC:40 Hz to 200 Hz (other ranges upon request)
standard measuring ranges
current: 0 A to 1 A and 0 A to 5 A (sinusoidal) or DC
Ri: 20 mΩ (5 A-input) or 100 mΩ (1 A-input)
over-load: 2-times, 4-times for max. 5 s
voltage: 0 V to 125 V and 0 V to 250 V AC or DC
Ri:       
600 kΩ (125 V-input) or 1.2 MΩ (250 V-input)
over-load:       
max. 500 V AC/DC
custom measuring ranges

voltage: end value in range 0.1 to 400 V AC/DC
Ri:
4.8 kΩ/V
over-load:       
5-times UN, max. 500 V AC/DC
current:       
end value in range 0.001 to 5 A AC/DC
Ri:       
100 mΩ ÷ (measuring range [A])
over-load:       
2-times, 4-times for max. 5 s
end value:       
adjustable ±5 %


output

output changing       

voltage/current:       
link between terminal 8 and 9
current output:       
0/4 mA to 20 mA selectable, burden ≤500 Ω
rise time (T90):       
<650 ms
burden error:       
<0.1 % (RL = <200 Ω), <0.2 % (RL = <500 Ω)
voltage:       
0/2 V to 10 V selectable, load max. 10 mA
      

housing

type:       
polycarbonate, UL 94 V-0
TS35 acc. to DIN EN 60715:2001-09

weight:       
approx. 200 g
connection:       
screw terminals, max. 2.5 mm2
ingress protection:       
housing IP30, terminals IP20 acc. to BGV A3




For further details p.r.t. data sheet:





instruction manual as .pdf:


 

 

 

Warenkorb

Sie haben noch keine Artikel in Ihrem Warenkorb.

Warenkorb »

Herzlich willkommen

E-Mail-Adresse:
Passwort:
Passwort vergessen?

Top Artikel