model:
125L: housing width 12.5 mm, auxiliary voltage 24 V DC +/- 15 %:
125LP: housing width 12.5 mm, auxiliary voltage 24 V DC +/- 15 % with carrier rail bus connection (+ 7,00 EUR) :
125M: housing width 12.5 mm, wide-range power supply 20 to 125 V DC, 20 to 253 V AC (+ 21,50 EUR) :
input:
0: universal input for Pt100, Pt1000 and thermocouple:
options MA:
01: push-in terminals (pluggable) (+ 7,35 EUR) :
accessories:
PRVK: power rail supply terminal (+ 4,55 EUR) :

Bitte beachten Sie stets die Bestellhinweise auf den einzelnen Datenblättern!

Product Description


general information:

Devices of the MU125 series convert a temperature measurement value or resistance measurement value from various sensors to a current signal of 4 mA to 20 mA. The universal configurability of the measuring inputs reduces the stock requirement for various applications. The housing width of only 12.5 mm enables space-saving installation in the switch cabinet.

  • universal input for Pt100, Pt1000, thermocouple, NTC and resistance measurement value
  • configuration via front DIP switches
  • analog actual value output 4 mA to 20 mA
  • zero point and limit value can be adjusted via trim potentiometers on the front
  • Pt100 and Pt1000 sensors: monitoring of sensor break and short-circuit
  • wide-range mains adapter or 24 V DC
  • optional supply via carrier rail bus
  • removable, coded screw terminals or optional push-in-terminals
  • housing width 12.5 mm
  • carrier rail mounting TS35 EN60715

specifications:

wide-range power supply - auxiliary voltage: 20 V DC to 125 V DC and
20 V AC to 250 V AC (47 Hz to 63 Hz), max.1.5 W
24 V power supply- auxiliary voltage:24 V DC +/-15 %, max. 1.5 W
rated voltage: 253 V AC
test voltage: 3k V AC between
auxiliary voltage // input = output
working temperature: -10°C to +60°C
storage temperature:-20°C to +80°C
humidity:10 % to 90 % (non-condensing)
measurement inputs:Pt100:                        linearised, measuring current approx.1.6 mA
Pt1000:                      linearised,
measuring current approx. 130 μA
                                    In the event of a sensor break or short circuit,
                                    the analog output drops to 0 mA. The
                                    operation LED blinks red
thermocouple:          linearised with reference junction
                                    compensation (optionally without internal
                                    compensation
NTC:                           linearised for B25/85 = 3,977 K or
                                    3,528 K, max. load 200 μW (averaged)
linear resistance:    Mb. 0...2 kΩ: approx. 1.4 mA
                                    Mbs. 0...5 kΩ, 0...10.kΩ: approx. 300 μA
analog output:4 mA to 20 mA, burden max. 400 Ω, no galvanic isolation from the input signal (max. burden error of 0.2 % at 400 Ohm)
dimensions
(W x D x H):
12.5 x 114 x 108 mm
weight:120 g
ingress protection:IP20




For further details p.r.t. data sheet: