humidity and temperature measurement transducer | GHTU-...-MP
Product Description
general information:
The humidity transducer offers even greater possibilities to compensate the special sensor characteristics due to the newest microprocessor technology. Regarding precision, temperature stability and functionality a new dimension is entered. The transducer can be used for almost all applications due to the different types (e.g. wall or channel mount, with separated probe tube or with heat absorption hat) and the wide temperature range (electronic: -25°C to +50°C; sensor: -40°C to +120°C), 2 standard signal outputs.
- GHTU-1R-MP: wall version, probe length: 50 mm (standard version)
- GHTU-1K-MP: wall and duct version, probe length: 220 mm (standard version)
- GHTU-2K-MP: duct version, probe length: 220 mm (standard version)
- GHTU-SHUT-MP: heat absorption hat / weather protection
- GHTU-KABEL-MP: wall version with cable and high humidity sensor
measuring range: |
relative humidity: 0.0 % to 100.0 % r.h. (temperature compensated) temperature: -40.0°C to +120.0°C or -40.0°F to +248°F |
recommended humidity range: |
20.0 % to 80.0 % r. h. (standard) 5.0 % to 95.0 % r. h. (with option high humidtiy) |
display options: | With option UNI an alternative display unit can be shown instead of the humidity measuring value. The unit selection is done via keyboard. wet bulb temperature: -27.0°C to +60.0°C dewpoint temperature: -40.0°C to +60.0°C enthalpy: -25.0 kJ/kg to +999.9 kJ/kg atmospheric humidity: 0.0 g/kg to 640.0 g/kg absolute humidity: 0.0 g/m3 to 200.0 g/m3 |
accuracy (at 25°C and in recommended humidity range): | display: humidity: ±2.5 % r.h. temperature: ±0.4 % of measured value ±0.2°C output signal: humidity ±0.2 % FS temperature ±0.2 % FS |
temperature compensation: | automatical |
auxiliary energy: | 12 V DC to 30 V DC or 18 V DC to 30 V DC (for output: 0 V to 10 V) |
reverse voltage protection: | 50 V, permanent |
perm. impedance (at 4 mA to 20 mA): | RA [Ω] ≤ (Uv [V] - 12 V) / 0.02 A |
perm. load (at 0 ... 1(10) V): | RL [Ω] > 3,000 Ω |
display: | approx. 10 mm high, 4-digit LCD display, alternating humidity and temperature display |
working temperature: | -25°C to +50°C (electronics) sensor head and tube: -40°C to +100°C - for short time up to +120°C |
storage temperature: | -25°C to +70°C |
relative humidity (electronics): |
0 % to 95 % r.h. (non-condensing); If there is a risk of condensation due to temperature changes, please use our encapsulated or lacquered types (OPTION „LACK“) |
housing: |
ABS (IP65) |
sensor tube: |
tube 14 mm Ø, with screw-type protection cap |
design type KABEL: | with separated sensor tube, sensor head (Ø1 4x 68 mm) connected to device via 1 m teflon cable, option high-humidty sensor incl. |
design type SHUT: | heat absorption hat / weather protection application: for outdoor measurements, strong solar radiation and rain do not distort the measurement design: heat absorption hat made of plastic, Ø 110 mm, height approx. 140 mm. Wall mounting panel made of stainless steel with 3 mounting holes for screws with maximal shaft diameter 5 mm. Largest overhang 160 mm. |
electrical connection: | elbow-type plug acc. to EN 175301-803/A (IP65) |
mounting: | 4 housing holes for wall mounting or by means of plastic tube clamp for duct mounting |
functions: | min/max value memory, offset and slope adjustable,output signal scaleable |