data logger | HD35ED-G-1NB-E
860,00 EUR
incl. 19 % VAT excl. shipping costs
delivery time processing time as may be necessary - please ask!
Product.Nr.: HD35ED-G-1NB-EProduct Description
wireless data logger for temperature, humidity and carbon dioxide (CO2), with display
general information:
HD35ED-G-1NB-E stores the measured values in its internal memory (44,000 samples) and transmits the acquired data to the base unit automatically at regular intervals or upon request. The sensors are all inside the housing. Calculated measurement quantities: dew point, wet bulb temperature, absolute humidity, mixing ratio, partial vapour pressure. Acoustic alarm with internal buzzer. Configuration via HD35-AP-S software or front keyboard. Power supply by internal battery. Installation with fixed or removable wall mount (supplied mount or optional flanges).
specifications:
humidity (r.h.): |
measuring principle: | capacitive |
measurement range: | 0 % to 100 % r.h. |
|
resolution: |
0.1 % r.h. |
|
accuracy (at +23°C): | ± 1.8 % r.h (0 % to 80 % r.h.) ± [1.8 + 0.11 * (r.h. -80)] % r.h. (remaining range) | |
working temperature: | -40°C to +105°C (r.h. max = [100-2 * (T-80)] at T = +80°C to +105°C) |
|
temperature T: |
sensor: | sensor integrated in humidity module |
measurement range: | -40°C to +105°C |
|
resolution: |
0.1°C |
|
accuracy: | ±0.2°C in the range 0°C to +60°C ±(0.2 – 0.05 * T)°C in the range T = -40°C to 0°C ±[0.2 + 0.032 * (T-60)]°C in the range T = +60°C to +105°C | |
carbon dioxide (CO2): |
sensor: | NDIR (non-dispersive infrared rays) |
measurement range: | 0 ppm to 5000 ppm |
|
resolution: |
1 ppm |
|
accuracy: | ±(50 ppm + 3 % of measured value) at +20°C and 1,013 hPa | |
working temperature: | -5°C to +50°C |
|
response time: |
T90 <120 s (air speed = 2 m/s) |
|
frequency of transmitting: | 868 MHz | |
transmitting range: | 300 m (E, J) / 180 m (U) in open field (can be reduced due to the presence of obstacles or adverse atmospheric conditions) | |
logging interval: | 10, 15, 30 s / 1, 2, 5, 10, 15, 30, 60 min | |
working temperature: |
-10°C to +70°C | |
relative working humidity: | 0 % to 85 % r. F., non-condensing | |
power supply: | internal, non-rechargeable lithium thionyl choride (Li-SOCl2) battery, 3.6 V, format 'AA', 2-pole Molex 5264 connector | |
battery life: | 1.5 years typical (without repeaters, measurement and logging interval 2 min) |
catalogue page as .pdf: |
Recommended products
repeater | HD35-RE-E324,00 EUR |
|
interface | HD35-AP-D-E156,50 EUR |
|
interface | HD35-AP-W-E521,00 EUR |
|
interface | HD35-AP-G-E498,00 EUR |
|
data logger | HD35ED-O-1NB-E770,00 EUR |
|
non-rechargeable 3.6 V lithium-thionyl chloride battery | HD35-BAT221,20 EUR |
|
alarm module | HD35-ED-ALM-E319,00 EUR |
|
software | HD35-AP-S68,30 EUR |
|
web data logger | HD 50...0,00 EUR |