temperature measuring transducer | GTMU-MP-AP
Product Description
freely scaleable Pt1000 temperature transducer
general information:The new generation of our temperature measuring transducers offers more flexibility due to state-of-the-art microprocessor technology.
Because of many different construction types and an measuring range of -50°C to +400°C nearly all kinds of applications can be covered.
- on-site display of temperature
- output signal freely scaleable
- user-adjustment possible
construction type 1 with process connection for direct screw
connection
|
für or high temperatures, with process connection and neck tube
|
indoor or outdoor probe
|
duct probe
|
specifications:
measuring range: | -50.0°C to +400.0°C, freely scaleable (The probe length should be selected in a way to ensure that the maximum permissible working temperature of the electronics and the housing of +70°C is not exceeded!) |
accuracy (at +25 °C): | display temp.: ±0.4 % of meas. value ±0.2°C output signal: ±0.2 % FS (compared to display) |
probe: | Pt1000, 2-wire, DIN class B |
output signal: | 4 mA to 20 mA (2-wire), freely |
auxiliary energy: | 12 V DC to 30 V DC or 18 V DC to 30 V DC (for output: 0- ... V) |
reverse voltage protection: | 50 V permanently |
permissible burden (at 4 mA to 20 mA): | RA [Ω] <
(Uv [V] - 12 V) / 0.02 A |
permissible load (at 0-1 (10) V): | RL [Ω] >3,000 Ω |
display: | approx. 10 mm high, 4-digit LCD display |
working temperature: | -25°C to +70°C (electronics) |
storage temperature: | -20°C to +70°C |
relative humidity (electronics): | 0 % to 95 % r.h. (non-condensing); if there is a risk of condensation due to temperature changes, please use our encapsulated or lacquered types (optional) |
type SHUT: | heat protective shield / weather protective shield application: for highly precise outdoor measurements, strong solar radiation and rain do not falsify the measurements. construction: heat protective shiels made of plastic, Ø 110 mm, height approx. 140 mm. Wall mounting made of stainless steel with 3 mounting holes diameter 5 mm. Largest overhang 160 mm. |
housing: | ABS (IP65) |
probe tube: | stainless steel |
mounting: | 4 holes in housing for wall mounting or plastic tube clamps for duct mounting |
electrical connection: | angle plug according to EN 175301-803/A (IP 65) |
functions: | min/max value memory, offset and slope digitally adjustable, output signal freely scaleable (without tools) |
catalogue page as .pdf: |
instruction manual as .pdf: |
Recommended products
longer probe for measuring transducer GTMU | GTMU-FL5,45 EUR |